POWERLEX® PVC HD Multicore Flexible Cords

Description
2C+E and 3C+E flexible copper conductors, 0.6/1kV V-90 insulated and PVC sheathed heavy duty flexible cord to AS/NZS 3191
Description
2C+E and 3C+E flexible copper conductors, 0.6/1kV V-90 insulated and PVC sheathed heavy duty flexible cord to AS/NZS 3191
Standards
National : AS/NZS 3191Description
- 0.6/1kV
- V-90 insulated and PVC sheathed heavy duty flexible cord to AS/NZS 3191.
Characteristics
Construction characteristics | |
---|---|
Outer sheath | PVC |
Insulation | V-90 |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Current carrying capacities single phase (in Amps)
- Insulation type: Thermoplastic
- Maximum conductor temperature: 75°C
- Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
-
- Unenclosed spaced
-
- Unenclosed touching
-
- Unenclosed and partially surrounded by thermal insulation
-
- Unenclosed and completely surrounded by thermal insulation
-
- Enclosed conduit in air
-
- Enclosed, partially surrounded by thermal insulation
-
- Enclosed, completely surrounded by thermal insulation
-
- Buried direct
-
- Underground ducts
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1 | 15 | 14 | 11 | 7 | 13 | 10 | 6 | 22 | 17 |
1.5 | 19 | 18 | 14 | 9 | 16 | 13 | 8 | 28 | 21 |
2.5 | 27 | 26 | 20 | 13 | 23 | 19 | 12 | 40 | 30 |
4 | 37 | 34 | 27 | 17 | 30 | 24 | 15 | 52 | 39 |
Current carrying capacities three phase (in Amps)
- Insulation type: Thermoplastic
- Maximum conductor temperature: 75°C
- Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
-
- Unenclosed spaced
-
- Unenclosed touching
-
- Unenclosed and partially surrounded by thermal insulation
-
- Unenclosed and completely surrounded by thermal insulation
-
- Enclosed conduit in air
-
- Enclosed, partially surrounded by thermal insulation
-
- Enclosed, completely surrounded by thermal insulation
-
- Buried direct
-
- Underground ducts A
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1 | 13 | 12 | 9 | 6 | 11 | 9 | 5 | 19 | 14 |
1.5 | 16 | 15 | 12 | 8 | 14 | 11 | 7 | 24 | 18 |
2.5 | 23 | 22 | 17 | 11 | 20 | 16 | 10 | 34 | 25 |
4 | 31 | 29 | 23 | 15 | 25 | 20 | 13 | 44 | 33 |