3.8/6.6kV Three Core

Description

Description

Standards

  • International
    IEC 60228; IEC 60502-2
  • National
    AS/NZS 1125; AS/NZS 1429.1

Construction

  • Stranded compacted conductor
  • Semi-conductive insulation screen
  • Copper wire screen
  • XLPE insulation
  • Semi-conductive conductor screen
  • PVC sheath

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
-
Conductor material
Copper
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted

Dimensional characteristics

Dimensional characteristics

Approximate weight
735.0 kg/100m
Conductor cross-section
185 mm²
Conductor diameter
16.1 mm
Diameter over insulation
22.227 mm
Diameter over screen
25.527 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
2.5 mm
Nominal overall diameter
61.8 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø

Electrical characteristics

Electrical characteristics

A.C. Conductor resist. 50Hz and at 90 °C
0.128 Ohm/km
Capacitance (All Main Cores - Screen)
0.53 µF / km
Charging current per phase
0.632 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
9.61 W/km
Inductive reactance at 50Hz
0.085 Ohm/km
Insulation resistance at 20°C
4600 MOhm.km
Max. DC resistance of the conductor at 20°C
0.099 Ohm/km
Maximum electric stress
1.7 kV/mm
Permissible short circuit current conductor 1s
26.4 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.043 Ohm/km
Zero sequence resistance at 20°C
0.896 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
38.85 kN

Usage characteristics

Usage characteristics

Minimum Bend Radius - During Installation (under Tension)
1110 mm
Minimum Bend Radius - Installed
740 mm

Resources

Resources

Current carrying capacity table (in Amps) - 3.8/6.6kV Three Core

Current carrying capacity table (in Amps) - 3.8/6.6kV Three Core
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al
185.0 436.0 338.0 472.0 365.0 319.0 247.0 429.0 333.0 348.0 270.0
In air touching (3 core)
In air spaced (3 core)
In air enclosed (3 core)
Direct Buried (3 core)
Underground ducts (3 core)

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close