XLPE/PVC SWA 4C+E 0.6/1kV Circular

Products

4x120mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMP23AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Stranded copper
  • Conductor cross-section: 120 mm²
  • Earth conductor cross section: 35 mm²
  • Maximum Pull Tension of Armour: 25 kN
  • Maximum Pulling Tension: 6.4 kN
  • Minimum Bend Radius - During Installation (under Tension): 960 mm
  • Minimum Bend Radius - Installed: 640 mm

 

4x150mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMP24AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Stranded copper
  • Conductor cross-section: 150 mm²
  • Earth conductor cross section: 50 mm²
  • Maximum Pull Tension of Armour: 25 kN
  • Maximum Pulling Tension: 6.9 kN
  • Minimum Bend Radius - During Installation (under Tension): 1040 mm
  • Minimum Bend Radius - Installed: 690 mm

 

4x16mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMP15AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Stranded copper
  • Conductor cross-section: 16 mm²
  • Earth conductor cross section: 6 mm²
  • Maximum Pull Tension of Armour: 9 kN
  • Maximum Pulling Tension: 3.1 kN
  • Minimum Bend Radius - During Installation (under Tension): 460 mm
  • Minimum Bend Radius - Installed: 310 mm

 

4x25mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMC17AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Compact copper
  • Conductor cross-section: 25 mm²
  • Earth conductor cross section: 6 mm²
  • Maximum Pull Tension of Armour: 11 kN
  • Maximum Pulling Tension: 3.4 kN
  • Minimum Bend Radius - During Installation (under Tension): 510 mm
  • Minimum Bend Radius - Installed: 340 mm

 

4x35mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMC18AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Compact copper
  • Conductor cross-section: 35 mm²
  • Earth conductor cross section: 10 mm²
  • Maximum Pull Tension of Armour: 12 kN
  • Maximum Pulling Tension: 3.7 kN
  • Minimum Bend Radius - During Installation (under Tension): 560 mm
  • Minimum Bend Radius - Installed: 370 mm

 

4x50mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMC19AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Compact copper
  • Conductor cross-section: 50 mm²
  • Earth conductor cross section: 16 mm²
  • Maximum Pull Tension of Armour: 17 kN
  • Maximum Pulling Tension: 4.3 kN
  • Minimum Bend Radius - During Installation (under Tension): 640 mm
  • Minimum Bend Radius - Installed: 430 mm

 

4x70mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMC20AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Compact copper
  • Conductor cross-section: 70 mm²
  • Earth conductor cross section: 25 mm²
  • Maximum Pull Tension of Armour: 20 kN
  • Maximum Pulling Tension: 4.9 kN
  • Minimum Bend Radius - During Installation (under Tension): 740 mm
  • Minimum Bend Radius - Installed: 490 mm

 

4x95mm2 + E XLPE/PVC SWA Circular Orange

Nexans ref. HTMC22AA004OMAA

  • Packaging: Cut to length (m)
  • Type of conductor: Compact copper
  • Conductor cross-section: 95 mm²
  • Earth conductor cross section: 25 mm²
  • Maximum Pull Tension of Armour: 23 kN
  • Maximum Pulling Tension: 5.5 kN
  • Minimum Bend Radius - During Installation (under Tension): 830 mm
  • Minimum Bend Radius - Installed: 550 mm

 

Description

Description

Standards

  • National
    AS/NZS 1125; AS/NZS 5000.1
  • 4 core+earth,
  • Circular,
  • 0.6/1kV
  • X-90 insulated,
  • PVC bedded,
  • Steel wire armoured,
  • PVC sheathed cable to AS/NZS 5000.1,
  • Copper conductors, 90°C.

 

 

Orange Circular; Circs; Armoured

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
Steel wires
Colour
Orange
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
X-90
Material of bedding
PVC
Outer sheath
PVC
With Green/Yellow core
Yes

Dimensional characteristics

Dimensional characteristics

Number of earth cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid

Resources

Resources

XLPE/PVC SWA Circular 3C+E and 4C+E - Current carrying capacities three phase (in Amps)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90

Maximum conductor temperature: 90°C

Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
1.0 16.0 14.0 12.0 7.0 13.0 10.0 6.0 22.0 16.0
1.5 20.0 19.0 15.0 9.0 16.0 13.0 8.0 28.0 20.0
2.5 28.0 26.0 21.0 13.0 24.0 19.0 12.0 39.0 29.0
4.0 38.0 35.0 28.0 18.0 30.0 24.0 15.0 51.0 37.0
6.0 48.0 45.0 36.0 22.0 38.0 30.0 19.0 63.0 46.0
10.0 66.0 62.0 49.0 31.0 53.0 42.0 26.0 85.0 63.0
16.0 88.0 83.0 66.0 41.0 68.0 55.0 34.0 110.0 81.0
25.0 119.0 111.0 89.0 56.0 91.0 73.0 46.0 143.0 107.0
35.0 147.0 137.0 110.0 69.0 114.0 91.0 57.0 172.0 130.0
50.0 180.0 168.0 134.0 0.0 136.0 108.0 0.0 204.0 155.0
70.0 229.0 213.0 170.0 0.0 173.0 138.0 0.0 251.0 193.0
95.0 283.0 263.0 210.0 0.0 209.0 167.0 0.0 302.0 233.0
120.0 330.0 306.0 245.0 0.0 246.0 197.0 0.0 344.0 270.0
150.0 377.0 350.0 280.0 0.0 277.0 222.0 0.0 385.0 304.0
185.0 436.0 404.0 323.0 0.0 322.0 257.0 0.0 435.0 348.0
240.0 517.0 479.0 383.0 0.0 386.0 309.0 0.0 504.0 411.0
300.0 594.0 549.0 0.0 0.0 0.0 0.0 0.0 567.0 463.0
400.0 685.0 632.0 0.0 0.0 0.0 0.0 0.0 640.0 524.0
500.0 779.0 718.0 0.0 0.0 0.0 0.0 0.0 714.0 601.0
Unenclosed spaced
Unenclosed touching
Unenclosed and partially surrounded by thermal insulation
Unenclosed and completely surrounded by thermal insulation
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure

Selling & delivery Information

Other colours are available on request.

Find a Distributor

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close