Skip to main content

If you can read this text, your browser is not interpreting this page as the designers intended. This may be because you are using an obsolete, non-standards compliant browser or you have Cascading Style Sheets disabled.Read more about Web Standards at Reactive.

Catalogue Products

 

CURRENT RATINGS - PVC FLEXIBLE CORDS

In accordance with AS/NZS 3008.1.

Nom. conductor areaCurrent carrying capacityMaximum DC resistance @ 20°C MulticoreMaximum DC resistance @ 20°C MulticoreVoltage drop single phaseVoltage drop 3 phase
mm2 A PACW Ohm/km TACW Ohm/km mV/A.m mV/A.m
0.5 3 39 40.1 94.9 82.2
0.75 7.5 26 26.7 63.3 54.8
1.0 10 19.5 20 47.5 41.1
1.5 15 13.3 13.7 32.3 28.0
2.5 20 7.98 8.21 19.4 16.8
4.0 25 4.95 5.09 12.0 10.4

Where a flexible cord is wound on a drum, multiply current carrying capacities by the following factor:

Number of layers 1 2 3 4
Derating factor 0.76 0.58 .047 0.40

back to product search